CANopen转CAN常见10个问题及解决方法

1.设备上电后无数据通信
1. No data communication after the device is powered on


检查电源电压是否匹配(通常9–36V),确认CANopen与CAN端终端电阻(120Ω)已接,总线无短路断路;重新上电复位,观察设备指示灯状态。
Check if the power supply voltage matches (usually 9-36V), confirm that the CANopen and CAN terminal resistors (120 Ω) are connected, and there is no short circuit or open circuit on the bus; Re power on and reset, observe the status of the device indicator lights.


2.CANopen端能通信,CAN端无数据
2. The CANopen end can communicate, but there is no data on the CAN end


确认转换模式(网关/透传)设置正确,检查CANopen节点ID、波特率、对象字典映射是否配置;重启设备使配置生效。
Confirm that the conversion mode (gateway/transparent transmission) is set correctly, and check if the CANopen node ID, baud rate, and object dictionary mapping are configured; Restart the device to make the configuration effective.


3.CAN端有数据,CANopen端收不到
3. There is data on the CAN end, but the CANopen end cannot receive it


核对PDO映射、COB‑ID与通信周期,确保发送端数据长度匹配;检查CANopen从站状态是否进入Operational,而非Pre‑operational。
Check PDO mapping, COB-ID, and communication cycle to ensure that the data length at the sender matches; Check if the CANopen slave status has entered Operational instead of Pre Operational.


4.总线报错、丢包、数据错乱
4. Bus errors, packet loss, and data confusion


优先统一两端波特率,CAN与CANopen必须一致;减少总线分支与干扰,走线远离强电,增加屏蔽接地。
Priority should be given to unifying the baud rates at both ends, and CAN and CANopen must be consistent; Reduce bus branching and interference, keep wiring away from strong electricity, and increase shielding grounding.


5.节点ID冲突无法通信
5. Node ID conflict prevents communication


修改设备拨码或软件配置,保证总线上每个CANopen设备ID唯一;重新搜索节点,清除冲突记录。
Modify device dialing or software configuration to ensure that each CANopen device ID on the bus is unique; Search for nodes again and clear conflict records.


6.NMT启动失败,无法进入运行状态
6. NMT failed to start and cannot enter the running state


检查主站NMT指令发送,确认从站无紧急报文;排查供电不稳、总线干扰或硬件故障,复位后重新配置。
Check the NMT command sent by the master station and confirm that there are no emergency messages from the slave station; Check for unstable power supply, bus interference, or hardware faults, reset and reconfigure.


7.数据长度不匹配(DLC错误)
7. Data length mismatch (DLC error)


统一收发端数据长度,CANopen PDO与CAN帧DLC保持一致;修改映射长度,避免超长或短帧导致丢弃。
Unify the length of data between the sender and receiver, and keep the CANopen PDO consistent with the CAN frame DLC; Modify the mapping length to avoid discarding frames that are too long or too short.


8.转换延迟大,实时性差
8. High conversion delay and poor real-time performance


关闭不必要的心跳、同步报文,缩短PDO发送周期;减少总线上节点数量,降低总线负载率。
Turn off unnecessary heartbeats, synchronize messages, and shorten the PDO sending cycle; Reduce the number of nodes on the bus and lower the bus load rate.


9.上电配置丢失,需重新设置
9. Power on configuration is lost and needs to be reset


配置完成后执行保存到Flash操作,避免断电丢失参数;检查是否有拨码开关覆盖软件配置。
After the configuration is completed, execute the save to Flash operation to avoid losing parameters due to power failure; Check if there is a dip switch covering the software configuration.


10.硬件指示灯异常、不亮或常红
10. Hardware indicator light is abnormal, not on, or constantly red


检查供电、接线顺序(CAN_H/CAN_L不要接反);替换终端电阻或测试设备,排除芯片损坏、总线静电击穿问题。
Check the power supply and wiring sequence (do not connect CAN_S/CAN_L in reverse); Replace terminal resistors or testing equipment to eliminate chip damage and bus static breakdown issues.


如果您的项目中有CANopen转CAN需求,可以加微信13019325660或前往沈阳广成科技官网进行具体咨询,欢迎来访。
If you have CANopen to CAN conversion requirements in your project, you can add WeChat 13019325660 or visit the official website of Shenyang Guangcheng Technology for specific consultation. Welcome to visit.